USA website link
KINETIC STORAGE TECHNOLOGY - Rotabloc Diesel UPS Systems
200kVA1000kVAintroductionsystem descriptionbenefitstechnical benefitscommercial benefitsmodule ratingssystem schematics

chevron Rotary UPS 200kVA+ : module ratings and dimensions

Type

Rotabloc

RB

150-5

RB

200-5

RB

250-5

RB

300-5

RB

400-5

Critical kVA
150
200
250
300
400

Critical kW - unity pf

Criticall kW - 0.8pf

150*

120

200*

160

250*

200

300*

240

400*

320

Rotabloc/alternator
length
2000
2265
2265
2265
2600
depth
1000
1000
1000
1000
1100
height
1200
1280
1280
1280
1400
Choke
length
400
500
500
600
600
depth
400
500
500
600
600
height
1600
1600
1600
1600
1800
Control cab
length
1000
1000
1000
1000
1000
depth
600
600
600
600
600
height
2000
2000
2000
2000
2000

The Rotabloc 'critical' output is fully rated, i.e. the 400kVA module gives 400kW at 1.0pf

Rotabloc

RB

500-5

RB

650-5

RB

800-5

RB

1000-5

Critical kVA
500
650
800
1000

Critical kW - unity pf

Critical kW - 0.8pf

500*

400

650*

520

800*

640

1000*

800

Rotabloc/alternator
length
2780
3270
3250
4750
depth
1100
1100
1100
1200
height
1400
1400
1400
1400
Choke
length
600
600
600
800
depth
600
600
600
800
height
1800
1800
1800
1800
Control cab
length
1000
1000
1000
1000
depth
600
600
600
600
height
2000
2000
2000
2000

The Rotabloc ‘critical’ output is fully rated, i.e. the 800kVA module gives 800kW at 1.0pf